AXL F BK PN XC Bus coupler

2701222

Axioline F, Bus coupler, PROFINET, RJ45 jack, Extreme conditions version, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector

The bus coupler is intended for use within a PROFINET network. The bus coupler creates the link to the Axioline F I/O system and the industrial I/O signals connected to it. Up to 63 Axioline F devices can be connected to the bus coupler. Device descriptions for Phoenix Contact controllers are integral parts of the engineering tools PC Worx and PLCnext Engineer. Corresponding GSDML files are available for integrating the Axioline F station into other programming systems. These files can be downloaded at: www.phoenixcontact.com/product/2701222

Dimensional drawing
Width 45 mm
Height 126.1 mm
Depth 74 mm
Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

PROFINET
Number of interfaces 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Transmission speed 100 Mbps (full duplex)
Transmission physics Ethernet in RJ45 twisted pair
Axioline F local bus
Number of interfaces 1
Connection method Bus base module
Transmission speed 100 Mbps
Service
Number of interfaces 1
Connection method Micro USB type B

System limits
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 63
PROFINET
Device function PROFINET device
Specification Version 2.2
Conformance Class Conformance-Class C
Device ID 1000hex
Vendor ID 00B0hex

Product type I/O component
Product family Axioline F
Type block modular
Mounting position any (observe temperature derating)
Scope of delivery including bus base module and Axioline F connector
Special properties Extreme conditions version
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 570 mA (2.0 A on UBus, UL = 24 V)
Power consumption max. 14 W (2.0 A on UBus, UL = 24 V)
Protective circuit Surge protection; electronic
Reverse polarity protection; electronic
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Power supply unit max. 2 A
Electrical isolation/isolation of the voltage ranges
Test voltage: PROFINET interface 1 / PROFINET interface 2 1500 V AC, 50 Hz, 1 min.
Test voltage: PROFINET interface 1 / 24 V communications voltage (UL) feed-in 1500 V AC, 50 Hz, 1 min.
Test voltage: PROFINET interface 2 / 24 V communications voltage (UL) feed-in 1500 V AC, 50 Hz, 1 min.
Test voltage: PROFINET interface 1 / functional ground 1500 V AC, 50 Hz, 1 min.
Test voltage: PROFINET interface 2 / functional ground 1500 V AC, 50 Hz, 1 min.
Test voltage: 24 V communications voltage (UL) feed-in / functional ground 500 V AC, 50 Hz, 1 min.

Connection technology
Connection name Axioline F connector
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.