IB IL TEMP 2 UTH-XC-PAC - Temperature module

2024-05-22T02:02:40Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:91314542948247498755105@112qq64.c311om

 

IB IL TEMP 2 UTH-XC-PAC Temperature module

2701216

Inline, Temperature measurement terminal, Analog UTH inputs: 2 (Thermocouples or linear voltage), connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field

The terminal is designed for use within an Inline station. This terminal can be used to acquire signals from standard thermocouples. It supports 13 different types of thermocouples according to DIN EN 60584-1 and DIN 43710, as well as a linear voltage input of -15 mV to +85 mV. Thanks to special engineering measures and tests, the terminal can be used under extreme ambient conditions.

Dimensional drawing
Width 12.2 mm
Height 136.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions

Inline local bus
Number of interfaces 2
Connection method Inline data jumper
Transmission speed 500 kbps

Module
ID code (dec.) 127
ID code (hex) 7F
Length code (hex) 02
Length code (dec) 02
Process data channel 32 bit
Input address area 4 Byte
Output address area 4 Byte
Register length 32 bit
Required parameter data 6 Byte
Required configuration data 4 Byte

Analog
Input name Analog UTH inputs
Description of the input Inputs for thermocouples or linear voltage
Number of inputs 2 (Thermocouples or linear voltage)
Connection method Inline connector
Connection technology 2-conductor
Note regarding the connection technology Shielded compensating line for TC with encapsulated sensors
A/D conversion time typ. 120 µs (per channel)
Sensor types that can be used (TC) U, T, L, J, E, K, N, S, R, B, C, W, HK
Measuring principle Successive approximation
Measured value representation 16 bits (15 bits + sign bit)
Process data update max. 30 ms (For both channels)
Protective circuit Surge protection (TC channels); up to ±40 V

Product type I/O component
Product family Inline
Type modular
Scope of delivery including Inline connector and labeling field
Operating mode Process data operation with 2 words
Special properties Extreme conditions version
Diagnostics messages Failure of the internal I/O supply I/O error message sent to the bus coupler
Failure of or insufficient communications power UL I/O error message sent to the bus coupler
I/O error Error message in the process data
User error Error message in the process data
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials
Power consumption typ. 587 mW
max. 882 mW
Potentials: Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current draw max. 60 mA
typ. 43 mA
Potentials: Supply of analog modules (UANA)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 18 mA
typ. 11 mA
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) 500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic)/functional ground 500 V AC, 50 Hz, 1 min.
Test voltage: 24 V analog supply (analog I/O)/functional ground 500 V AC, 50 Hz, 1 min.

Connection technology
Connection name Inline connector