AXL F UTH8 1F Temperature module

2688417

Axioline F, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps

Module
Input address area 18 Byte
Output address area 18 Byte
Required parameter data 27 Byte (20 bytes for configuration with GSD AXL UTH 8 (packed))
Required configuration data 7 Byte

Analog
Input name Analog inputs
Description of the input Inputs for thermocouples or linear voltage
Number of inputs 8 + 1 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V)
Connection method Push-in connection
Connection technology 2-conductor (shielded, twisted pair)
A/D converter resolution 24 bit
Sensor types (RTD) that can be used Pt 100 (4 external cold junctions, can also be used as a sensor input)
Sensor types that can be used (TC) U, T, L, J, E, K, N, S, R, B, C, W, HK
Measuring principle Sigma/Delta process
Measured value representation 16 bits (15 bits + sign bit)
Input filter time 40 ms
60 ms
100 ms
120 ms (adjustable)
Protective circuit Short-circuit protection, overload protection of the inputs
Transient protection of inputs

Product type I/O component
Product family Axioline F
Type block modular
Mounting position any (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!)
Scope of delivery including bus base module and Axioline F connectors
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials
Power consumption typ. 1.63 W (entire device)
max. 2.58 W (entire device)
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 180 mA
typ. 115 mA
Power consumption max. 0.9 W
typ. 0.55 W
Potentials: Supply for analog modules (UA)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 70 mA
typ. 45.3 mA
Power consumption max. 1.68 W
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / functional ground 500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground 500 V AC, 50 Hz, 1 min.

Connection technology